• fuse-base (possibly including terminal covers and phase barriers)
  • fuse-link with blade contact
  • fuse-link replacement device (LV HRC fuse puller)

Since the design of this system cannot guarantee non-interchangeability of rated current, it must be handled by a qualified professional. NH-fuse links „gTr“ are used for the protection of transformers. The time/current characteristic is especially adapted to that of the protected transformer and implies optimal selectivity to NH-fuse links characteristic gG. The fuses can be loaded with 1×3 times nominal current for up to 10 hours. The fuse link operates at 1×5 times nominal transformer current within 2 hours.